Does the alarm occur during pre-purging? If so, replace the flame detection sensor (ZUV II).
Does the steam pressure exceed 0.98 MPa? If so, perform a full blow, set the steam pressure to 0, and check for blockages in the copper pipe or piping to which the pressure sensor is connected.
Does the alarm recur after restarting the boiler? If it does recur, it should be checked by a maintenance contractor.