If fuel valves (pilot gas piping and main gas piping) are closed, open them.
Is the flame detection sensor (ZUVⅡ) installed correctly? If it is off from the mounting base, install it correctly.
Is the ignition cord cap correctly installed? If not, attach it to the spark rod correctly.
Are there any spots of the ignition cord where the sheath has been torn off and the wires are exposed? If so, please replace the parts.
Are the U, V, and W wires of the blower in the control box disconnected from the terminals? If there is any disconnection, install the wiring after turning off the main power supply.
Is the wiring of the damper motor disconnected? If there is a disconnection, turn off the main power supply and repair the disconnected part.
Is the gas solenoid valve (pilot and main) wiring disconnected? If there is a disconnection, turn off the main power and repair the disconnection.
Does the alarm recur when the boiler is restarted? If the alarm recurs, it should be checked by a maintenance contractor.